Installer Menu
3-24 SlideSmart DC Installation and Reference Manual Revision D
8
0 = solo operator
1 = Loop Layout/Site #1
2 = Loop Layout/Site #2
Programs and establishes communication protocols when
wiring two operators as sequential gates. This menu item
only appears if the Dual Gate (DG) is set to 0.
Note: Use the most up-to-date version of S.T.A.R.T. and
make sure both operator’s have the same software
version loaded on the SDC. Press the RESET
button to display the version of software on your
operator.
3-wire shielded cable to
DUAL GATE input
terminals on both
operators. Pair wires:
A - A, COM - COM,
and B - B
9
0 = AC powered charger
1 = solar powered charger
Assigns charger type.
Note: If a solar-powered unit is ordered and delivered
factory-ready, this menu will not appear.
(N/A)
10
0 = standard (8Ah)
1 = extended (50Ah)
2 = maximum (110Ah)
Assign the battery type used by the operator.
Note: Smaller batteries are charged with less current to
avoid overheating and larger batteries are charged
with more current to supply a more rapid charge.
Extended (50Ah)
batteries require wire
extensions and shelf
installation.
Maximum (110Ah)
batteries require separate
housing and wiring.
11
0 = disabled
1 = enabled
Enables the Fire Department Open input.
When set to 1, the open signal received by the operator
overrides all photoelectric eyes and edge sensors and opens
the gate. Pressing the RESET button (or the OPEN push
button) is required before the gate can be closed.
+24V DC
EMERG OPEN
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
) Tasks and Explanations
Associated
DC Controller
Connections
Display
SG 0 (OFF)
SEQUENCED GATE
CH 0 (AC)
CHARGER TYPE
BT 0 (STANDARD)
BATTERY TYPE
FO 0 (OFF)
FIRE DEPT OPEN