Installer Menu
Revision D Display and Menu Options 3-27
21
0 = IES reverses full open
1 = 2 second reversal only
The default setting is a two-second duration reversal if the
inherent sensor is triggered. The optional setting of 0 will
cause the gate to reopen fully if triggered while closing.
N/A
22
0 = Normally Open PE output
1 = Normally Closed
(supervised)
The default setting is photo eyes with Normally Open
outputs. The optional setting 1 requires a Normally Closed
(NC) output which requires that both a photo EYE OPEN
and a photo EYE CLOSE are connected. If set for NC, the
connection is also supervised and any open or short circuit
fault will generate a FAULT 2 alert which requires a STOP
button reset to re-enable any function if triggered.
Photo eye connections:
EYE OPEN
EYE CLOSE
EYE COM
+24V
23
0 = Normally Open Edge
1 = Normally Closed
The default setting is edge sensor with Normally Open
(NO) output. The optional setting of 1 requires an (NC)
output.
EDGE
COM
24
0 = Disable Free Exit
1 = Disable Close Timer
Configures the BLOCK EXIT input to disable either the
Free Exit Detector function or, alternately, the Timer To
Close function. The default setting disables the free exit
detector.
Note: The free exit is disabled when the gate is at its closed
limit. If the closed limit is not tripped, the free exit
continues to work normally.
BLOCK EXIT
COM
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
) Tasks and Explanations
Associated
DC Controller
Connections
Display
SR 1 REVERSE 2S
IES SENSOR LOGIC
PC 0 NO CONTACT
PHOTO EYE OUTPUT
GC 0 NO CONTACT
GATE EDGE OUTPUT
DT 0 FREE EXIT
DISABLE FUNCTION