Installer Menu
3-26 SlideSmart DC Installation and Reference Manual Revision D
16
0 = 80 Seconds max run,
1 = 300 Seconds max run
Assigns a motor run time of 80 or 300 seconds. If the gate
opening or closure takes longer than 80 seconds, you’ll need
to set the run timer to 1.
(N/A)
17
0 = OFF
7 = 7 ft, 8 = 8ft, through
32 = 32 ft
Sets the distance (from the closed gate position) where the
gate stops in a partial open.When a number is entered in
the PO display, the open partial input becomes operational.
OPEN PARTIAL
COM
18
0 = Close eye stops only
1 = 2s reverse to open
The default setting is non-reversal if the close photo eye is
triggered. A setting of 1 causes the gate to reverse and travel
open for two seconds if triggered while closing.
EYE CLOSE
EYE COM
19
0 = Open eye stops only
1 = 2s reverse to close
The default setting is non-reversal if the open photo eye is
triggered. A setting of 1 causes the gate to reverse travel and
close for two seconds if triggered while opening.
EYE OPEN
EYE COM
20
0 = Edge reverses full open
1 = 2s reversal only
The default setting is a full-open reversal if the gate edge is
triggered while closing. The optional setting of 1 causes the
gate to reverse for two seconds if triggered while closing.
EDGE
COM
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
) Tasks and Explanations
Associated
DC Controller
Connections
Display
RT 0 (80 SECS)
MAXIMUM RUN TIMER
PO 0 (OFF)
PARTIAL OPEN
EC 0 (STOP ONLY)
EYE CLOSE LOGIC
EO 0 (STOP ONLY)
EYE OPEN LOGIC
GR 0 (FULL OPEN)
GATE EDGE LOGIC