Installer Menu
Revision D Display and Menu Options 3-25
12
0 = maximum sensitivity
2 = moderate sensitivity
9 = least sensitivity
Adjusts the sensitivity of the internal inherent entrapment
sensor (IES). Available settings are 0 to 9 with 9 being the
least sensitive. HySecurity strongly recommends that you
avoid setting the IES sensitivity higher than 6.
Note: Before changing the IES sensitivity, make sure that
the gate rolls smoothly without obstruction. Fix any
issues with gate hardware.
See Note.
13
0 = stop, reverse for 2s
1 = stop only
In a Usage Class 4 environment, the operator can be set to
stop the gate and not reverse gate travel after an IES trip.
Note: This menu option only appears when the Usage
Class is set to 4.
(N/A)
14
0 = no delay
1 through 20 in ½ second
increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set up as a Master or a
Slave. Available settings are 1 through 20. Each increment
adds ½ second time delay following a command to close
before the operator activates. Provides up to a 10 second
time delay.
DUAL GATE inputs on
both operators
15
0 = no delay
1 through 20 in ½ second
increments
For example:
1 = ½ second
10 = 5 seconds
20 = 10 seconds
Only appears if the gate operator is set up as a Master or a
Slave. Available settings are 1 through 20. Each increment
adds ½ second time delay following a command to open
before the operator activates. Provides up to a 10 second
time delay.
DUAL GATE inputs on
both operators
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
) Tasks and Explanations
Associated
DC Controller
Connections
Display
SS 0 (OFF)
IES STOP ONLY
LC 0 (0.0 SECS)
LEAF DELAY CLOSE
LO 0 (0.0 SECS)
LEAF DELAY OPEN